LEWPLC

G7T-112S OMRON ราคา 550 บาท

฿550.00
G7T-112S OMRON ราคา 550 บาท
เหลือ 0 ชิ้น
ซื้อเลย
หยิบลงตะกร้า
  • หมวดหมู่ : Stock Project 2
  • รหัสสินค้า : 002682

รายละเอียดสินค้า G7T-112S OMRON ราคา 550 บาท

 

Product classification Monostable relays
Standard type
Coil ratings 24 VDC 21 mA
Coil resistance 1150 Ohm
Operate voltage (Set voltage) 80% Max.
Release voltage (Reset voltage) 10% Min.
Max. voltage 110% (of rated voltage)
Power consumption (Single stable) 0.5 W
Operating indicator Not equipped
Coil surge killer Not equipped
Contact Type SPDT
Contact method Single
Contact material Contact body material: Ag alloy
Contact finish: Nothing
Contact rated load 220 VAC 2 A (Resistive load)
220 VAC 1 A (Inductive load (cos phi = 0.4))
24 VDC 5 A (Resistive load)
24 VDC 2 A (Inductive load (L/R = 7 ms))
Maximum switching voltage 250 VAC (Resistive load)
250 VAC (Inductive load (cos phi = 0.4))
125 VDC (Resistive load)
125 VDC (Inductive load (L/R = 7 ms))
Maximum switching current AC: 5 A (Resistive load)
AC: 5 A (Inductive load (cos phi = 0.4))
DC: 5 A (Resistive load)
DC: 5 A (Inductive load (L/R = 7 ms))
Maximum switching power AC: 440 VA (Resistive load)
AC: 220 VA (Inductive load (cos phi = 0.4))
DC: 120 W (Resistive load)
DC: 48 W (Inductive load (L/R = 7 ms))
Failure rate 10 mA at 5 VDC (failure level: P Reference value)
Ambient temperature Operating: -40 to 70 CEL
(with no icing or condensation)
Ambient humidity Operating: 5 to 85% RH
(with no icing or condensation)
Characteristics
Contact resistance Max. 50 mOhm, Measuring the voltage drop across the contacts by applying test voltage/current as 5 VDC 1 A
Operating time (set time) 15 ms Max.
Release time (Reset time) 15 ms Max.
Max.operating frequency (Mechanical) 18000 opn./h
Max.operating frequency (Erectrical) 1800 opn./h
Insulation resistance Between coil and contacts: 100 MOhm Min. (at 500 VDC)
Between contacts of same polarity: 100 MOhm Min. (at 500 VDC)
Dielectric strength Between coil and contacts: 2000 VAC 50/60 Hz for 1 min (Leakage current 2 mA 50/60 Hz 1 min)
Between contacts of same polarity: 1000 VAC 50/60 Hz for 1 min (Leakage current 2 mA 50/60 Hz 1 min)
Vibration resistance (Destruction) 10 to 55 to 10 Hz 0.5-mm single amplitude (1.0-mm double amplitude) for 2 hours each in X, Y, and Z directions (No defect in appearance and construction after applying variable vibration in each directions for 2 hours.)
Vibration resistance (Malfunction) 10 to 55 to 10 Hz 0.5-mm single amplitude (1.0-mm double amplitude) in each direction
Shock resistance (Destruction) 200 m/s**2 each direction 3 times (No defect in appearance and construction after applying shock in each directions 3 times.)
Shock resistance (Malfunction) 200 m/s**2
Endurance (Mechanical) 50000000 operations Min.
Endurance (Electrical) 1000000 operations Min.
Protective structure Closed type (cover)
Applicable standard (UL) Standard No.: UL508
File No.: E41643
Applicable standard (CSA) Standard No.: C22.2 No.14
File No.: LR35535
Terminal structure Plug-in