General Specifications
Display73.5 mm x 104 mm
Battery8 AA alkaline cells, IEC LR6
Dimensions (H x W x L)184 mm x 211 mm x 93 mm
Weight1.3 kg
Temperature
Operating temperature-10 °C  to +50 °C
 Storage temperature-20 °C to +60 °C
Operating humidityNon-condensing (<10 °C)
≤80 % RH (10 °C to 30 °C)
≤50 % RH (30 °C to 50 °C)
Altitude
Operating altitude2000 m
Storage altitude12000 m
Overvoltage categoryCAT IV 600 V
Safety
GeneralIEC 61010-1, pollution degree 2
IEC 61010-2-033:CAT IV 600 V
IEC 61557-1
Insulation resistance measurementIEC 61557-2
Effectiveness of protective measuresIEC 61557-16
IP RatingIEC 60529 IP40
Electromagnetic Compatibility (EMC)
InternationalIEC 61326-1: Electromagnetic environment for portable equipments
IEC 61326-2-2 CISPR 11: Group 1, Class A

Group 1: Equipment has intentionally generated and/or uses conductively-coupled radio frequency energy that is necessary for the internal function of the equipment itself.

Class A: Equipment is suitable for use in all establishments other than domestic and those directly connected to a low-voltage power supply network that supplies buildings used for domestic purposes. There may be potential difficulties in ensuring electromagnetic compatibility in other environments due to conducted and radiated disturbances.
Caution: This equipment is not intended for use in residential environments and may not provide adequate protection to radio reception in such environments.

Electrical Specifications
The meter’s accuracy is specified for one year after calibration at operating temperatures of 10°C to 30°C. For operating temperatures outside the range (-10°C to +10°C and +30°C to +50°C), add ± 0.25% per °C, except on the 20% bands, add ± 1% per °C.
Insulation resistance testing
Test voltageRangeResolutionAccuracy
250 V<200 kΩUnspecifiedUnspecified
200 kΩ to 500 kΩ1 kΩ0.05
0.50 MΩ to 5.00 MΩ10 kΩ0.05
5.0 MΩ to 50.0 MΩ100 kΩ0.05
50 MΩ to 500 MΩ1 MΩ0.05
0.50 GΩ to 5.00 GΩ10 MΩ0.05
5.0 GΩ to 50.0 GΩ500 MΩ0.2
>50 GΩUnspecifiedUnspecified
500 V<200 kΩUnspecifiedUnspecified
200 kΩ to 500 kΩ1 kΩ0.05
0.50 MΩ to 5.00 MΩ10 kΩ0.05
5.0 MΩ to 50.0 MΩ100 kΩ0.05
50 MΩ to 500 MΩ1 MΩ0.05
0.50 GΩ to 5.00 GΩ10 MΩ0.05
5.0 GΩ to 10.0 GΩ100 MΩ0.05
10.0 GΩ to 50.0 GΩ500 MΩ0.2
50 GΩ to 100 GΩ5 GΩ0.2
>100 GΩUnspecifiedUnspecified
1000 V<200 kΩUnspecifiedUnspecified
200 kΩ to 500 kΩ1 kΩ0.05
0.50 MΩ to 5.00 MΩ10 kΩ0.05
5.0 MΩ to 50.0 MΩ100 kΩ0.05
50 MΩ to 500 MΩ1 MΩ0.05
0.50 GΩ to 5.00 GΩ10 MΩ0.05
5.0 GΩ to 0.0 GΩ100 MΩ0.05
20.0 GΩ to 50.0 GΩ500 MΩ0.2
50 GΩ to 200 GΩ5 GΩ0.2
>200 GΩUnspecifiedUnspecified
2500 V<200 kΩUnspecifiedUnspecified
200 kΩ to 500 kΩ1 kΩ0.05
0.50 MΩ to 5.00 MΩ10 kΩ0.05
5.0 MΩ to 50.0 MΩ100 kΩ0.05
50 MΩ to 500 MΩ1 MΩ0.05
0.50 GΩ to 5.00 GΩ10 MΩ0.05
5.0 GΩ to 50.0 GΩ100 MΩ0.05
50 GΩ to 500 GΩ5 GΩ0.2
>500 GΩUnspecifiedUnspecified

Bar graph range: 0 Ω to 1 TΩ Insulation test voltage accuracy: -0 %, +10 % @ 1 mA load current Charging rate for capacitive load: 5 s/μF Discharging rate for capacitive load: 1.5 s/μF

RangeAccuracy
Leakage current measurement1 nA to 2 mA±(20 % + 2 nA)
Capacitance measurement0.01 μF to 2.00 μF±(15 % rdg + 0.03 μF)
Test voltage for insulation resistance250 V to 2500 V±(3 % + 3 V)
Warning for energized circuitWarning range
>30 V
Timer (F1537 only)RangeResolution
0 to 99 minSetting: 1 min
Alert: 1 s
Short circuit current
F1535>2mA
F1537>5mA
ACV/DCV/resistance measurement (1537 only)
FunctionRangeResolutionAccuracy
±(% rdg + dgt)
VAC0 V to 600.0 V0.1 V±(2 % +10)
(45 Hz to 500 Hz)
VDC0 V to 600.0 V0.1 V±(2 % +10)
Resistance0Ω to 600.0Ω0.1Ω±(2 % +10)
600Ω to 6000Ω1Ω
6.00 kΩ to 60.00kΩ10Ω