| Accuracy | |
| Voltage | Range: 1000 V Maximum resolution: 0.1 V Intrinsic accuracy at reference conditions (% of reading + % of full scale): ±(0.2% + 0.01%) |
| Frequency | Range: 42.5 to 69 Hz Maximum resolution: 0.01 Hz Intrinsic accuracy at reference conditions (% of reading + % of full scale): ±(0.1%) |
| Aux Input | Range: ±10 V dc Maximum resolution: 0.1 mV Intrinsic accuracy at reference conditions (% of reading + % of full scale): ±(0.2% + 0.02%) |
| Voltage Min/Max | Range: 1000 V Maximum resolution: 0.1 V Intrinsic accuracy at reference conditions (% of reading + % of full scale): ±(1% + 0.1%) |
| Current Min/Max | Range: Defined by accessory Maximum resolution: Defined by accessory Intrinsic accuracy at reference conditions (% of reading + % of full scale): ±(5% + 0.2%) |
| THD on Voltage | Range: 1000% Maximum resolution: 0.1% Intrinsic accuracy at reference conditions (% of reading + % of full scale): ±0.5 |
| THD on Current | Range: 1000% Maximum resolution: 0.1% Intrinsic accuracy at reference conditions (% of reading + % of full scale): ±0.5 |
| Voltage Harmonics 2nd ...50th | Range: 1000 V Maximum resolution: 0.1 V Intrinsic accuracy at reference conditions (% of reading + % of full scale): ≥10 V: ±5% of reading, <10 V: ±0.5 V |
| Current Harmonics 2nd ...50th | Range: Defined by accessory Maximum resolution: Defined by accessory Intrinsic accuracy at reference conditions (% of reading + % of full scale): ≥3% of current range: ±5% of reading, <3% of current range: ±0.15% of range |
| Unbalance | Range: 100% Maximum resolution: 0.1% Intrinsic accuracy at reference conditions (% of reading + % of full scale): ±0.2 |
| Power Supply | |
| Voltage Range | 100 to 500 V using safety plug input when powering from the measurement circuit 100 to 240 V using standard power cord (IEC 60320 C7) |
| Power Consumption | Maximum 50 VA (max. 15 VA when powered using IEC 60320 input) |
| Efficiency | ≥68.2% (in accordance with energy efficiency regulations) |
| Maximum No-Load Consumption | <0.3 W only when powered using IEC 60320 input |
| Mains Power Frequency | 50/60 Hz ± 15% |
| Battery | Li-ion 3.7 V, 9.25 Wh, customer-replaceable |
| On-Battery Runtime | Four hours in standard operating mode, up to 5.5 hours in power saving mode |
| Charging Time | <6 hours |
| Data Acquisition | |
| Resolution | 16-bit synchronous sampling |
| Sampling Frequency | 10.24 kHz at 50/60 Hz, synchronized to mains frequency |
| Input Signal Frequency | 50/60 Hz (42.5 to 69 Hz) |
| Circuit Types | 1-ø, 1-ø IT, split phase, 3-ø delta, 3-ø wye, 3-ø wye IT, 3-ø wye balanced, 3-ø Aron/Blondel (2-element delta), 3-ø delta open leg, currents only (load studies) |
| Data Storage | Internal flash memory (not user replaceable) |
| Memory Size | Typical 10 logging sessions of 8 weeks with 1-minute intervals and 500 events |
| Basic Interval | |
| Measured Parameters | Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy |
| Averaging Interval | User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min |
| Averaging Time Min/Max Values | Voltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30) Aux, Power: 200ms |
| Demand Interval (Energy Meter Mode) | |
| Measured Parameters | Energy (Wh, varh, VAh), PF, maximum demand, cost of energy |
| Interval | User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off |
| Power Quality Measurements | |
| Measured Parameter | Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD |
| Averaging Interval | 10 min |
| Individual Harmonics | 2nd ...50th harmonic |
| Total Harmonic Distortion | Calculated on 50 harmonics |
| Events | Voltage: dips, swells, interruptions, current: inrush current |
| Triggered Recordings | Full cycle RMS updated every half cycle of voltage and current (Urms1/2 according to IEC61000-4-30) Waveform of voltage and current |
| Standards Compliance | |
| Harmonics | IEC 61000-4-7: Class 1 IEEE 519 (short time harmonics) |
| Power Quality | IEC 61000-4-30 Class S, IEC62586-1 (PQI-S device) |
| Power | IEEE 1459 |
| Power Quality Compliance | EN50160 (for measured parameters) |
| Interfaces | |
| USB-A | File transfer via USB flash drive, firmware updates, max. supply current: 120 mA |
| WiFi | File transfer and remote control via direct connection or WiFi infrastructure |
| Bluetooth | Read auxiliary measurement data from Fluke Connect® 3000 series modules (requires 1738, or 1736 upgrade option) |
| USB-Mini | Data download device to PC |
| Voltage Inputs | |
| Number of Inputs | 4 (3 phases and neutral) |
| Maximum Input Voltage | 1000 Vrms, CF 1.7 |
| Input Impedance | 10 MΩ |
| Bandwidth | 42.5 Hz to 3.5 kHz |
| Scaling | 1:1 and variable |
| Measurement Category | 1000 V CAT III/600 V CAT IV |
| Current Inputs | |
| Number of Inputs | 4, mode selected automatically for attached sensor |
| Input Voltage | Clamp input: 500/50 mVrms; CF 2.8 |
| Rogowski Coil Input | 150/15 mVrms at 50 Hz, 180/18 mVrms at 60 Hz; CF 4; all at nominal probe range |
| Range | 1 to 150/10 A to 1500 A with thin flexible current probe i17XX-flex1500 12" 3 to 300/30 A to 3000 A with thin flexible current probe i17XX-flex3000 24" 6 to 600/60 A to 6000 A with thin flexible current probe i17XX-flex6000 36" 40 mA to 4/0.4 A to 40 A with 40 A clamp i40s-EL |
| Bandwidth | 42.5 Hz to 3.5 kHz |
| Scaling | 1:1 and variable |
| Auxiliary Inputs | |
| Number of Inputs | 2 |
| Input Range | 0 to ±10 V dc, 1 reading/s |
| Scale Factor | Format: mx + b (gain and offset) user configurable |
| Displayed Units | User configurable (7 characters, for example, °C, psi, or m/s) |
| Wireless Connection | |
| Number of Inputs | 2 |
| Supported Modules | Fluke Connect® 3000 series |
| Acquisition | 1 reading/s |
| Environmental Specifications | |
| Operating Temperature | 14 to 122°F (-10 to 50°C) |
| Storage Temperature | −4 to 140°F (-20 to 60°C) With battery: −4 to 122°F (-20 to 50°C) |
| Operating Humidity | 50 to 86°F (10 to 30°C) max. 95% RH 86 to 104°F (30 to 40°C) max. 75% RH 104 to 122°F (40 to 50°C) max. 45% RH |
| Operating Altitude | 6561.68' (2000 m) (up to 13123.36' (4000 m) derate to 1000 V CAT II/600 V CAT III/300 V CAT IV) |
| Storage Altitude | 39,370.079' (12,000 m) |
| Enclosure | IP50 in accordance with EN60529 |
| Vibration | MIL-T-28800E, Type 3, Class III, Style B |
| Safety | IEC 61010-1 IEC Mains Input: Overvoltage Category II, Pollution Degree 2 Voltage Terminals: Overvoltage Category IV, Pollution Degree 2 IEC 61010-2-031: CAT IV 600 V / CAT III 1000 V |
| Electromagnetic Compatibility (EMC) | EN 61326-1: Industrial CISPR 11: Group 1, Class A Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment) USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103 |
| Temperature Coefficient | 0.1 x accuracy specification/°C |
| General Specifications | |
| Color LCD Display | 4.3" (109.22 mm) active matrix TFT, 480 pixels x 272 pixels, resistive touch panel |
| Tamper Protection | Kensington lock slot |
| Dimensions | Instrument: 7.8 x 6.6 x 2.2" (19.8 x 16.7 x 5.5 cm) Power supply: 5.1 x 5.1 x 1.8" (13.0 x 13.0 x 4.5 cm) Instrument with power supply attached: 7.8 x 6.6 x 3.5" (19.8 x 16.7 x 9 cm) |
| Weight | Instrument: 2.5 lb (1.1 kg) Power supply: 0.9 lb (400 g) |