Fluke 1732/EUS Specifications

Voltage
Range1000 V
Resolution0.1 V
Intrinsic Accuracy at Reference Conditions
(% of Reading +% of Full Scale)
±(0.2% + 0.01%)
Current: Direct Input i17xx-flex 1500 12"
Range150 A
1500 A
Resolution0.1 A
1 A
Intrinsic Accuracy at Reference Conditions
(% of Reading +% of Full Scale)
±(1% + 0.02%)
±(1% + 0.02%)
Current: Direct Input i17xx-flex 3000 24"
Range300 A
3000 A
Resolution1 A
10 A
Intrinsic Accuracy at Reference Conditions
(% of Reading +% of Full Scale)
±(1% + 0.03%)
±(1% + 0.03%)
Current: Direct Input i17xx-flex 6000 36"
Range600 A
6000 A
Resolution1 A
10 A
Intrinsic Accuracy at Reference Conditions
(% of Reading +% of Full Scale)
±(1.5% + 0.03%)
±(1.5% + 0.03%)
Current: Direct Input i40s-EL Clamp
Range4 A
40 A
Resolution1 mA
10 mA
Intrinsic Accuracy at Reference Conditions
(% of Reading +% of Full Scale)
±(0.7% + 0.02%)
±(0.7% + 0.02%)
Frequency
Range42.5 to 69 Hz
Resolution0.01 Hz
Intrinsic Accuracy at Reference Conditions
(% of Reading +% of Full Scale)
±(0.1%)
Auxillary Input
Range±10 V dc
Resolution0.1 mV
Intrinsic Accuracy at Reference Conditions
(% of Reading +% of Full Scale)
±(0.2% + 0.02%)
Voltage Min/Max
Range1000 V
Resolution0.1 V
Intrinsic Accuracy at Reference Conditions
(% of Reading +% of Full Scale)
±(1% + 0.1%)
Current Min/Max
RangeDefined by accessory
ResolutionDefined by accessory
Intrinsic Accuracy at Reference Conditions
(% of Reading +% of Full Scale)
±(5% + 0.2%)
THD on Voltage
Range1000%
Resolution0.1%
Intrinsic Accuracy at Reference Conditions
(% of Reading +% of Full Scale)
±0.5
THD on Current
Range1000%
Resolution0.1%
Intrinsic Accuracy at Reference Conditions
(% of Reading +% of Full Scale)
±0.5
Power Supply
Voltage Range100 to 500 V using safety plug input when powering from the measurement circuit
100 to 240 V using standard power cord (IEC 60320 C7)
Power ConsumptionMaximum 50 VA (max. 15 VA when powered using IEC 60320 input)
Efficiency≥68.2% (in accordance with energy efficiency regulations)
Maximum No-Load Consumption≤0.3 W only when powered using IEC 60320 input
Mains Power Frequency50/60 Hz ±15%
BatteryLi-ion 3.7 V, 9.25 Wh, customer-replaceable
On-Battery RuntimeFour hours in standard operating mode, up to 5.5 hours in power saving mode
Charging Time<6 hours
Data Acquisition
Resolution16-bit synchronous sampling
Sampling Frequency10.24 kHz at 50/60 Hz, synchronized to mains frequency
Input Signal Frequency50/60 Hz (42.5 to 69 Hz)
Circuit Types1-φ, 1-φ IT, Split phase, 3-φ delta, 3-φ wye, 3-φ wye IT
3-φ wye balanced, 3-φ Aron/Blondel (2-element delta)
3-φ delta open leg, Currents only (load studies)
Data StorageInternal flash memory (not user replaceable)
Memory SizeTypical 10 logging sessions of 8 weeks with 1-minute intervals and 500 events
Basic Interval
Measured ParametersVoltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy
Averaging IntervalUser selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
Averaging Time Min/Max ValuesVoltage, Current: Full cycle RMS updated every half cycle Aux, Power: 200ms
Demand Interval (Energy Meter Mode)
Measured ParametersEnergy (Wh, varh, VAh), PF, maximum demand, cost of energy
IntervalUser selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off
Standards Compliance
PowerIEEE 1459
Interfaces
USB-AFile transfer via USB flash drive, firmware updates max. current: 120 mA
WiFiFile transfer and remote control via direct connection or WiFi infrastructure
USB-MiniData download device to PC
Voltage Inputs
Number of Inputs4 (3 phases and neutral)
Maximum Input Voltage1000 Vrms, CF 1.7
Input Impedance10 MΩ
Bandwidth (-3 dB)42.5 Hz to 3.5 kHz
Scaling1:1 and variable
Measurement Category1000 V CAT III/600 V CAT IV
Current Inputs
Number of Inputs3, mode selected automatically for attached sensor
Input VoltageClamp input: 500 mVrms/50 mVrms; CF 2.8
Rogowski Coil Input150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4; all at nominal probe range
Range1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 12"
3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 24"
6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 36"
40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL
Bandwidth (-3 dB)42.5 Hz to 3.5 kHz
Scaling1:1 and variable
Auxiliary Inputs
Number of Inputs2
Input Range0 to ±10 V dc, 1reading/s
Scale FactorFormat: mx + b (gain and offset) user configurable
Displayed UnitsUser configurable (7 characters, for example, °C, psi, or m/s)
Wireless Connection
Number of Inputs2
Supported ModulesFluke Connect® 3000 series
Acquisition1 reading/s
Environmental Specifications
Operating Temperature14 to 122 °F (-10 to 50°C)
Storage Temperature-4 to 140°F (-20 to 60°C)
With battery: -4 to 122 °F (-20 to 50°C)
Operating Humidity50 to 86°F (10 to 30°C) max. 95% RH
86 to 104°F (30 to 40°C) max. 75% RH
104 to 122°F (40 to 50 °C) max. 45% RH
Operating Altitude6561.7' (2000 m) [up to 13,123.4' (4000 m) derate to 1000 V CAT II/600 V CAT III/300 V CAT IV]
Storage Altitude39,370' (12,000 m)
EnclosureIP50 in accordance with EN60529
VibrationMIL-T-28800E, Type 3, Class III, Style B
SafetyIEC 61010-1
IEC Mains Input: Overvoltage Category II, Pollution Degree 2
Voltage Terminals: Overvoltage Category IV, Pollution Degree 2
IEC 61010-2-031: CAT IV 600 V / CAT III 1000 V
Electromagnetic CompatibilityEN 61326-1: Industrial CISPR 11: Group 1, Class A
Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment)
USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103
Temperature Coefficient0.1 x accuracy specification/°C
General Specifications
Color LCD Display4.3" (109 mm) active matrix TFT, 480 pixels x 272 pixels, resistive touch panel
DimensionsInstrument: 7.8 x 6.6 x 2.2" (198 x 167 x 55 mm)
Power supply: 5.1 x 5.1 x 1.8" (130 x 130 x 45 mm)
Instrument with power supply attached: 7.8 x 6.6 x 3.5" (198 x 167 x 0.9 mm)
WeightInstrument: 2.5 lbs (1.1 kg)