| AC/DC Voltage Measurement | |
| Accuracy | Range: 600 V Resolution: 0.1 V 50 to 400 Hz ± (%of Rdg + Digits): ±(2% + 3) |
| Input Impedance | 3 MΩ (nominal), <100 pF |
| Common Mode Rejection Ratio (1 kΩ unbalanced) | >60 dB at DC, 50 or 60 Hz |
| Overload Protection | 600 V rms or DC |
| Earth Bond Resistance Measurement | |
| Range/Resolution | 20 Ω:0.01 Ω 200 Ω:0.1 Ω 2000 Ω:1 Ω 20k Ω:0.01 kΩ |
| Accuracy | ±(1.5% + 3) |
| Overload Protection | 2 V rms or DC |
| Open Circuit Test Voltage | >4 V, <8 V |
| Short Circuit Current | >200 mA |
| Insulation Specifications | |
| Measurement Range | 0.01 to 2000 MΩ |
| Test Voltage | 500 V, 1000 V |
| Test Voltage Accuracy | +20%, -0% |
| Short Circuit Current | 1 mA nominal |
| Auto Discharge | Discharge time <0.5 second for C = 1 µF or less |
| Live Circuit Indicator | Inhibit test if terminal voltage >30 V prior to initialization of test |
| Maximum Capacitive Load | Operable with up to 1 µF load |
| Measure Accuracy | 500 V: ±(1.5% + 5) 1000 V: ±(1.5% + 5) to 2000 MΩ, ±(10% + 3) above 2000 MΩ |