| AC/DC Voltage Specifications | |
| Range | 600.0 V |
| Resolution | 0.1 V |
| Accuracy | 50 Hz to 400 Hz: ±(2% of rdg + 3 digits) |
| Input Impedance | 3 MΩ (nominal), < 100 pF |
| Common Mode Rejection Ratio (1 kΩ unbalanced) | >60 dB at DC, 50 or 60 Hz |
| Overload Protection | 600 V RMS or DC |
| Earth Bond Resistance Specifications | |
| Range | 20.00 Ω to 20.00 kΩ |
| Resolution | 0.01 Ω to 0.01 kΩ |
| Accuracy | ±(1.5% + 3 digits) |
| Overload Protection | 2 V RMS or DC |
| Open Circuit Test Voltage | >4.0 V, <8 V |
| Short Circuit Current | >200.0 mA |
| Insulation Specifications | |
| Measurement Range | 0.01 MΩ to 10 GΩ |
| Test Voltage | 50, 100, 250, 500, 1000 V |
| Test Voltage Accuracy | +20%, -0% |
| Short Circuit Current | 1 mA nominal |
| Auto Discharge | Discharge time <0.5 second for C = 1 µF or less |
| Live Circuit Indicator | Inhibit test if terminal voltage >30 V prior to initialization of test |
| Maximum Capacitive Load | Operable with up to 1 µF load |
| Live Circuit Detection | Inhibit test if terminal voltage > 30 V prior to initialization of test |
| Maximum Capacitive Load | Operable with up to 1 µF load |
| Measure Accuracy | 50 V: ±(3% + 5) 100 V: ±(3% + 5) 250 V: ±(3% + 5) 500 V: ±(3% + 5) 1000 V: ±(3% + 5) to 2000 MΩ, ±(10% + 3) above 2000 MΩ |


This website uses cookies (Learn more) and has a privacy policy (Learn more).