| Range | 0.5 A to 400.0 A |
|---|---|
| Resolution | 0.1 A |
| Accuracy | 400.0 A: 2 % ± 5 digits (10 Hz to 100 Hz), 2.5 % ± 5 digits (100 Hz to 500 Hz) |
| Inrush | Max displayed reading: 999.9A |
| Crest factor (50 Hz/60 Hz) | 3 at 500 A, 2.5 at 600 A, 1.42 at 1000 A, add 2 % for C.F. > 2 |
| LCD w/backlight | 3½ digits |
| Log rate/interval | 1 sec minimum/adjustable by PC |
| Battery type | 2 AA, NEDA 15 A, IEC LR6/td> |
| Battery life | 400 hours |
| Memory | Record up to 65,000 readings |
| RF communications | 2.4 GHZ ISM Band |
| RF communication range | Open air, unobstructed: Up to 20 m Obstructed, sheetrock wall: Up to 6.5 m Obstructed, concrete wall or steel electrical enclosure: Up to 3.5 m |
| Operating temperature | -10 °C to +50 °C |
| Storage temperature | -40 °C to +60 °C |
| Temperature coefficient | Add 0.1 x (specified accuracy)/°C (< 18 °C or > 28 °C) |
| Operating humidity | 90% at 35 °C, 75 % at 40 °C, 45 % at 50 °C |
| Altitude | Operating: 2,000 m Storage: 12,000 m |
| EMC | EN 61326-1:2006 |
| Safety compliance | IEC 61010-1, 600 V CAT III, 3rd edition Pollution Degree 2 |
| Safety rating | CAT III 600 V |
| Certifications | CSA, CE, FCC: T68-FBLE IC: 6627A-FBLE |
| Ingress Protection (IP) rating | IP30 |
| Pollution Degree | 2 |
| Jaw opening | 34 mm (1.33 in) |
| Size (HxWxD) | 20.3 cm x 7.49 cm x 3.55 cm (8 in x 2.95 in x 1.4 in) |
| Weight | .22 kg (8 oz) |


This website uses cookies (Learn more) and has a privacy policy (Learn more).