| height |
47 mm
|
|
|---|---|---|
| width |
40 mm
|
|
| depth |
104 mm
|
|
| terminals description ISO n°1 |
(13-14)NO
|
|
| product weight |
0.17 kg
|
|
| resistance to high pressure washer |
7000000 Pa at 55 °C,distance: 0.1 m
|
|
| contacts usage |
Standard contacts
|
|
| positive opening |
With positive opening conforming to EN/IEC 60947-5-1 appendix K
|
|
| operating travel |
1.5 mm (NC changing electrical state)
2.6 mm (NO changing electrical state) 4.3 mm (total travel) |
|
| operating force |
44 N
|
|
| mechanical durability |
300000 cycles
|
|
| tightening torque |
0.8...1.2 N.m conforming to EN 60947-1
|
|
| shape of screw head |
Cross head compatible with Philips no 1 screwdriver
Cross head compatible with pozidriv No 1 screwdriver Slotted head compatible with flat Ø 4 mm screwdriver Slotted head compatible with flat Ø 5.5 mm screwdriver |
|
| contacts material |
Silver alloy (Ag/Ni)
|
|
| short-circuit protection |
10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
|
|
| [Ith] conventional free air thermal current |
10 A conforming to EN/IEC 60947-5-1
|
|
| [Ui] rated insulation voltage |
600 V (degree of pollution: 3) conforming to EN 60947-1
|
|
| [Uimp] rated impulse withstand voltage |
6 kV conforming to EN 60947-1
|
|
| [Ie] rated operational current |
3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1
6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1 0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1 0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1 0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1 1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1 |
|
| electrical durability |
1000000 cycles, AC-15, 2 A at 230 V, operating rate: <= 3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 3 A at 120 V, operating rate: <= 3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C 1000000 cycles, AC-15, 4 A at 24 V, operating rate: <= 3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C 1000000 cycles, DC-13, 0.2 A at 110 V, operating rate: <= 3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C 1000000 cycles, DC-13, 0.5 A at 24 V, operating rate: <= 3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C |
|
| electrical reliability |
Λ < 10exp(-6) 5 V 1 mA in clean environment EN/IEC 60947-5-4
Λ < 10exp(-8) 17 V 5 mA in clean environment EN/IEC 60947-5-4 |
|
| device presentation |
Complete product
|


This website uses cookies (Learn more) and has a privacy policy (Learn more).