| General Technical Data | |
| product brand name | SIRIUS |
| Size of the contactor | S0 |
| Protection class IP / on the front | IP20 |
| Degree of pollution | 3 |
| Installation altitude / at a height over sea level / maximum (m) | 2,000 |
| Ambient temperature / during operating (°C) | -25 … +60 |
Mechanical operating cycles as operating time
|
|
| Main Circuit | |
| Number of NC contacts / for main contacts | 0 |
| Number of NO contacts / for main contacts | 3 |
Operating current (A)
|
|
Service power
|
|
| Control Circuit | |
| Voltage type / of control feed voltage | DC |
Operating range factor control supply voltage rated value / of the magnet coil
|
|
| Pull-in power / of the solenoid / for DC (W) | 5.4 |
| Holding power / of the solenoid / for DC (W) | 5.4 |
| Auxiliary Circuit | |
| Contact reliability / of the auxiliary contacts | 1 faulty switching per 100 million (17 V, 1 mA) |
| Number of NC contacts / for auxiliary contacts / instantaneous switching | 0 |
| Number of NO contacts / for auxiliary contacts / instantaneous switching | 0 |
| Short-circuit | |
Design of the fuse link
|
|
| Installation/mounting/dimensions | |
| Mounting type | screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022 |
| series installation | Yes |
| Width (mm) | 45 |
| Height (mm) | 85 |
| Depth (mm) | 101 |
| Distance, to be maintained, to earthed part / sidewards (mm) | 6 |
| Connection Type | |
Design of the electrical connection
|
|
Type of the connectable conductor cross-section
|
|