FN-XY16SC41 PROFACE
| Item | Specification | ||
|---|---|---|---|
| Model No. | FN-XY16SC41 | ||
| Electrical | Rated Voltage | DC24V | |
| Rated Voltage Range | DC20.4 to DC28.8V | ||
|
Allowable Voltage Interruption |
10ms or less (Power supply: DC24V) | ||
| Power Consumption | 2.5W or less | ||
| Voltage Endurance |
AC500V, 10mA for up to 1minute (between power/ Input and Output, and FG terminals) |
||
| Insulation Registance |
10MΩ or more at DC500V (between power/ Input and Output, and FG terminals) |
||
| In-rush Current | 30A or less | ||
| Environmental | Operating Temperature | 0℃ to 55℃ | |
| Storage Temperature | -25℃ to 70℃ | ||
| Operating Humidity |
5 to 95% RH (Wet bulb temperature 39℃ or less. Non-condensing) |
||
| Storage Humidity |
5 to 95% RH (Wet bulb temperature 39℃ or less. Non-condensing) |
||
| Protection Rating | IP20 | ||
| Input/Output | Rated Input Voltage | DC24V | |
| Max. Input Voltage | DC28.8V | ||
| No. of Input Points | 16 points (sink/source type - dual use) | ||
| Input ON Voltage | DC15V or higher | ||
| Input OFF Voltage | DC5V or less | ||
| Input Impedance | 4.2kΩ | ||
| Input Delay Time | OFF-ON | 1.5ms or less | |
| ON-OFF | 1.5ms or less | ||
| Rated Output Voltage | DC24V | ||
| Rated Output Voltage Range | DC20.4 to DC28.8V | ||
| No. of Output Points | 16 points (source type) | ||
| Output Current |
0.2A/point (16 points/common, max. common current :1.6A) |
||
| Output Protection | None | ||
| Built-in Fuse |
3.5A, DC125V buit-in Chip Fuse (cannot be replaced) |
||
|
Voltage Drop (ON Voltage) |
DC1.5V or less | ||
| Clamp Voltage | DC39V ±1V | ||
| Current Leakage | 0.1mA or less | ||
| Output Delay Time | OFF-ON | 1ms or less | |
| ON-OFF | 1ms or less | ||
| Occupied Node Number | 1 | ||