Yes: input and output points: 4096 points, input and output device points: 8192 points, program capacity: 60K steps basic instruction processing speed (LD X0): 34ns Program Memory capacity: 240K bytes peripheral connection ports:, RS232 memory card I / F USB
Input and output of a multi-count controllable
As the actual input and output points that can access the input and output unit that is mounted to the base unit, CPU unit, supports (X/Y0 ~ FFF) 4096 points. In addition, it supports up to (X/Y0 ~ 1FFF) 8192 points as input and output device points that can be used for remote I / O station MELSECNET / H remote I / O network, such as CC-Link data link. |
The high-speed processing
I realized high-speed processing of the operation. · LD instruction processing speed: 34ns In addition, the high-speed system bus of the MELSEC-Q Series base unit, I realized the speed of the link refresh of the network unit and access to the intelligent function unit. |
Efficiency of debugging with high-speed communication with the programming tool
In response to high-speed communication up to 115.2kbps by RS-232, such as a monitor of time and write / read of the program is reduced, communication time efficiency of debugging has been improved. In addition, you can perform high-speed communication of 12Mbps with USB support. |
Can be connected to the extension base unit up to a 7-stage
CPU unit can be connected to the extension base unit of up to 7 stage. In addition, the total length of the extension cable is up to 13.2m, placement of the extension base unit with a high degree of freedom is possible. |
Input and output unit of AnS / A series, special function unit is available
You can (QA1S6 □ B, QA6 □ B, QA6ADP + A5 □ B/A6 □ B) the extension base unit of AnS / A Series, using the special function unit input and output unit of AnS / A series. |
The space-saving size due to downsizing
Mounting area of the Q series, to achieve the downsizing of approximately 60% as compared to the AnS series. |
Can be extended by the memory of the memory card
It is equipped with a memory card connector mounting, can be installed in the memory card of up to 32M bytes. (ATA card when using 32M bytes) By mounting the memory card of large capacity, it is possible to perform file management large set of comments to all data devices, memory and directly as the correction history past programs making it possible to hold within. In addition, even if you have not installed the memory card, ROM of the program can be the standard ROM that is built into the CPU unit, this can handle any file register by standard RAM. |
Can be forced ON / OFF of external I / O
CPU Unit is in RUN state, by the operation of the programming tool, force ON / OFF of external I / O can be run regardless of the state of the program. In addition, you can without having to STOP state of the CPU unit, to perform the wiring and operation test forced ON / OFF of the output. |
Can be automatically written to the standard ROM
It is possible to write to standard ROM of the CPU unit without using a programming tool parameter program of memory card. If you are doing a boot operation using standard ROM, because it fitted with a memory card to the CPU unit, writing can be a standard ROM the parameter program of the memory card, to carry programming tool (PC) for rewriting the parameter program eliminates the need. |
Can be set remote password
If there is an access from the external Ethernet module, serial communication unit, the modem interface unit, I can be selected whether or not access to the CPU unit by the remote password. |
Remote I / O net of MELSECNET / H can
It can be fitted with a remote master station of MELSECNET / H, to build a remote I / O system of MELSECNET / H. |
Supports multi-CPU system
CPU unit is compatible with multi-CPU system. Construction of multi-CPU system can be a combination of CPU unit, motion CPU, PC CPU module, the C Controller module. |
Support for redundant power supply system
By using redundant base unit, a redundant power supply module, CPU unit is capable of redundant power supply unit. By even when the power supply while the other unit fails, to supply power from the power supply unit to the other, you can continue driving. |