Product series / family name
VarPlusBox HDuty
Main function
Capacitor (Low Voltage)
Sub-range name
GB
Rated Voltage (AC) - Phase-to-phase
400 V
Rated impulse voltage (Uimp)
8 kV
Rated current
(400Vac; 50Hz) 36.1 A
(400Vac; 60Hz) 43.3 A
(400Vac; 60Hz) 43.3 A
Rated reactive power (Q)
(380Vac; 50Hz) 22.6 kVAr
(400Vac; 50Hz) 25 kVAr
(415Vac; 50Hz) 26.9 kVAr
(380Vac; 60Hz) 27.1 kVAr
(400Vac; 60Hz) 30 kVAr
(415Vac; 60Hz) 32.3 kVAr
(400Vac; 50Hz) 25 kVAr
(415Vac; 50Hz) 26.9 kVAr
(380Vac; 60Hz) 27.1 kVAr
(400Vac; 60Hz) 30 kVAr
(415Vac; 60Hz) 32.3 kVAr
Power dissipation/losses
11.3 W
Type of network
3-phase
Application type
Networks with significant non-linear loads
Network frequency
50/60 Hz
Capacitance
165.7 μF
Maximum continuous operating voltage (Uc)
(1.1xUn; 8h max.) 456.5 V
Compliant with standard(s)
IEC60831-1/2
Class
NLL max. 20%
Insulation class D
Insulation class D
Electrical durability (with load)
(1 year) 7 000 operations
Electrical durability
130 000 hours
Mounting mode
Plate mounting
Upright
Upright
Mounting location
Indoor
Net Height (mm)
355 mm
Net Width (mm)
309 mm
Net Depth (mm)
153 mm
Net weight
7.5 kg
Shape
Box type
Degree of protection
IP20
Material
Sheet steel enclosure (Casing)
Polypropylene (PP) dielectric film (special resistivity & profile; special wave-cut edge); metallized with Zn/Al alloy
Polyurethene (PUR) sticky dry resin; non-PCB (Impregnation)
Polypropylene (PP) dielectric film (special resistivity & profile; special wave-cut edge); metallized with Zn/Al alloy
Polyurethene (PUR) sticky dry resin; non-PCB (Impregnation)
Type of terminals
(Power) Bushing terminals
Functions
Low Voltage (LV) capacitor bank (3-phase)
Minimum temperature
-25 °C
Maximum temperature