FN-xx04AH11 PROFACE
Specification |
FN-xx04AH11 -> Replacement Comparison of 2-channel analog input/output units |
|||
---|---|---|---|---|
Model No. |
FN-AD04AH11 |
FN-DA04AH11 |
||
Electrical | Rated Voltage | DC24V | ||
Rated Voltage Range | DC20.4 to DC28.8V | |||
Allowable Voltage Drop | 10ms or less (Power supply: DC24V) | |||
Power Consumption | 4.8W or less | 7.2W or less | ||
Voltage Endurance |
AC1500V, 10mA for up to 1minute (between power/ Input and Output, and FG terminals), AC500V for up to 1minute (between primary and secondary power supplies) |
|||
In-rush Current | 30A or less | |||
Insulation Resistance |
10MΩ or more at DC500V (between charging and FG terminals) |
|||
Environmental |
Ambient Operating Temperature |
0℃ to 55℃ | ||
Storage Temperature |
-25℃ to 70℃ | |||
Ambient Humidity |
30 to 90% RH (Wet bulb temperature 39℃ or less. Non-condensing) |
|||
Storage Humidity |
30 to 90% RH (Wet bulb temperature 39℃ or less. Non-condensing) |
|||
Protecting Rating | IP30 | |||
Structural | Mounting Method | 35-mm DIN track or screw mounting | ||
External Dimensions | W168mm[6.61in.] × H50mm[1.97in.] × D50mm[1.97in.] | |||
Input/Output | Resolution | 12 bit | ||
Output/Input Channels | 4ch (fixed) | |||
Conversion Time | 2ms or less/channel | |||
Input/ Output Range Switch |
Depends on rotary switch settings | |||
Input/Output Range |
Voltage |
0 to 5V (impedance 1MΩ) |
0 to 5V (impedance 1kΩ) |
|
1 to 5V (impedance 1MΩ) |
1 to 5V (impedance 1kΩ) |
|||
0 to 10V (impedance 1MΩ) |
0 to 10V (impedance 1kΩ) |
|||
-5 to 5V (impedance 1MΩ) |
-5 to 5V (impedance 1kΩ) |
|||
-10 to 10V (impedance 1MΩ) |
-10 to 10V (impedance 1kΩ) |
|||
Current |
0 to 20mA (impedance 200Ω) |
0 to 20mA (impedance 400Ω)*1 |
||
4 to 20mA (impedance 200Ω) |
4 to 20mA (impedance 400Ω)*1 |
|||
Accuracy | 0.3%/FS (25℃), 0.5%/FS ( 0 to 55℃) | |||
Insulation Method | input terminals/ between internal circuits: Photocoupler Insulation | between output terminal and internal circuit: Photocoupler isolation | ||
Processing (after conversion) |
Simple Average, Running average (Exclude max./min. values) |
- | ||
Conversion Timing |
Simultaneous (all channnels, not selectable) |
|||
Calibration Function |
Offset, Gain settig Setting the upper limit value/ lower limit value for each range via switch |
This website uses cookies (Learn more) and has a privacy policy (Learn more).