Cylinder type sensing head size |
M30 |
Type |
Unshielded |
Sensing method |
Inductive type |
Sensing distance |
18 mm -10% to +10% |
Setting distance |
0 to 14 mm |
Differential distance |
10% Max. of sensing distance |
Sensing object |
Ferrous metal (Sensitivity lowers with non-ferrous metals.) |
Standard sensing object |
Iron 54*54*1mm |
Response frequency |
AC: 25 Hz (average) |
Power supply voltage |
24 to 240 VAC |
Operating voltage range |
20 to 264 VAC |
Leakage current |
1.7 mA Max. |
Control output (Output type) |
AC 2-wire models |
Control outpu (Switching capacity) |
5 to 300 mA |
Indicator |
Operation indicator(red) |
Operation mode |
NO |
Protective circuit |
Surge suppressor |
Ambient temperature |
Operating: -40 to 85 ℃
Storage: -40 to 85 ℃
(with no icing or condensation) |
Ambient humidity |
Operating: 35 to 95% RH
Storage: 35 to 95% RH
(with no condensation) |
Temperature influence |
+/- 10% Max. of sensing distance in temperature range of -25 to +70 CEL
+/- 15% Max. of sensing distance in temperature range of -40 to +85 CEL
(As the basis for sensing distance of 23CEL) |
Voltage influence |
+/- 1% Max. of sensing distance in rated voltage range +/- 15%. (As the basis for sensing distance at standard power voltage) |
Insulation resistance |
50 M OHM Min. at 500VDC between charged parts and the case |
Dielectric strength |
4000 VAC 50/60 Hz for 1 minute between charged parts and the case |
Vibration resistance |
10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions |
Shock resistance |
1000m/s2 for 10 times each in X, Y, and Z directions |
Degree of protection |
IEC60529: IP67
Company standard: Oil-proof |
Applicable standard (EC Directive (Low Voltage Directive) ) |
EN60947-1
EN60947-5-2 |
Applicable standard (EC Directive (EMC)) |
EMI: EN60947-5-2
Emission Enclosure: CISPR11 Group 1 class A
EMS: EN60947-5-2
Immunity ESD: IEC61000-4-2
Immunity RF-interference: IEC61000-4-3
Immunity Conducted Disturbance: IEC61000-4-6
Immunity Burst: IEC61000-4-4
CE marking: Equipped |
Applicable standard (CCC mark) |
Equipped |
Connection method |
Pre-wired models (Cable length: 2 m) |
Weight (Packed state) |
approx. 175 g |
Material (case) |
Brass nickel plating |
Material (sensing surface) |
PBT |
Material (clamping nuts) |
Brass nickel plating |
Material (toothed washer) |
Iron zinc plating |
Accessories |
Instruction manual
|