Function | Total Counter |
---|---|
Rated supply voltage | Not required External supply voltage(powered by built-in battery) |
Counter (Count range) | 0 to 99999999 |
Counter (Max. counting speed) |
20 Hz Minimum counting input signal width: 25 ms(ON/OFF ratio: 1:1) |
Counter (Input mode) | Increment |
Counter (Reset system) | External and manual reset |
Input signal | Count input ,Reset |
Input method | Free voltage input |
No-voltage input (No-contact input) |
Short-circuit (ON) impedance: 10 kOhm max. Residual voltage: 0.5 V max. (Actual performance 1.0 V) Open circuit impedance: 750 kOhm min. |
Voltage input |
Hight level: 24 to 240 VAC/VDC Low level: 0 to 2.4 VAC/VDC Input resistance: Approx. 4.7 kOhm |
Minimum input signal width | External reset: 20 ms |
Display method | 7-segment transmissive LCD |
Digit | 8 digit |
Character height |
Count value: 8.6 mm (Black) Zero suppression: Equipped |
Prescaling function | Not provided |
Key protection | Key protect Switch |
Teaching function | Not provided |
Batch counting function | Not provided |
Communications | Not provided |
Memory backup | Battery |
Battery life | For 7 years min. (with continuous input at 25CEL) |
Surrounding air temperature |
Operating: -10 to +55 CEL (With no icing or condensation) Storage: -25 to +65 CEL (With no icing or condensation) |
Ambient humidity |
Operating: 25% to 85% Storage: 25% to 85% |
Insulation resistance |
100 MOhm min. (at 500 VDC) Between current-carrying terminals and exposed non-current-carrying metal parts / Between count input terminals and reset terminals |
---|---|
Dielectric withstand voltage |
Between count input terminals and exposed non-current-carrying metal parts: 3700 VAC 50/60 Hz for 1 min Between reset terminals and exposed non-current-carrying metal parts: 2200 VAC 50/60 Hz for 1 min Between count input terminals and reset terminals: 2200 VAC 50/60 Hz for 1 min |
Impulse withstand voltage |
Between current-carrying terminal and exposed non-current -carrying metal parts: 4.5 kV Between count input terminals and reset terminals: 3.0 kV |
Noise immunity |
Between count input terminals: +-1.5k V Between reset terminals: +-500 V Square-wave noise by noise simulator (Pulse width: 100 ns/1 us, 1-ns rise) |
Static immunity | 8 kV (malfunction) |
Vibration resistance (Destruction) | 10 to 55 Hz with 0.375 mm single amplitude for two hours each in three directions |
Vibration resistance (Malfunction) | 10 to 55 Hz with 0.15 mm single amplitude for ten minutes each in three directions |
Shock resistance (Destruction) | 300 m/s2 three times each in six directions |
Shock resistance (Malfunction) | 200 m/s2 three times each in six directions |
Degree of protection |
Case front: IP66, NEMA 4 (indoors), and UL Type 4X (indoors)(when using the Y92S-32 Waterproof Packing and Y92F-30 Flush Mounting Adapter) Terminal block: IP20 |
Applicable standard (UL) |
Standard No.: UL863 File number: E67871 |
Applicable standard (CSA) |
Standard No.: CSA C22.2 No.14 File number: LR22310 |
Applicable standard (VDE) | VDE0106/P100 |
Applicable standard (LR) | Approved |
Applicable standard (EC Directive (Machinery Directive)) | EN61010-1 |
Applicable standard (EC Directive (Low Voltage Directive)) | EN61010-1 |
Applicable standard (EC Directive (EMC Directive)) |
EMI: EN61326 Emission Enclosure: EN55011 Group 1 Class B EMS: EN61326 Immunity ESD: EN61000-4-2 (4 kV contact discharge (level 2);8 kV air discharge (level 3)) Radiated electromagnetic field immunity: EN61000-4-3 (10 V/m (Amplitude-modulated, 80 MHz to 1 GHz) (level 3);10 V/m (Pulse-modulated, 900 MHz +-5 MHz) (level 3)) Immunity Conducted Disturbance: EN61000-4-6 (10 V (0.15 to 80 MHz) (level 3)) Immunity Burst: EN61000-4-4 (2 kV power-line;2 kV I/O signal-line) |
Mounting method | Flush mounting |
External connection method | Screw terminals |
Case color | Black (Munsell N1.5) |
Attachment | Flush mounting adapter, Waterproof rubber packing, Shock Prevention Cover |
Weight |
Approx. 60 g |